Complete catalogue

Download our extensive catalogue and discover many more products from REO.

PASSIVE CURRENT TRANSFORMER Series IN (PIN – Version)

Measuring Transducer (PIN-Version)

Description

The increasing development and widespread use of electronic devices with higher operating frequencies require current transformers with an extended frequency range. This requirement can be met with specially selected materials in conjunction with an optimized design.

Advantages (Electrical)

  • electrical
  • PIN connection according to UL 94 V-0
  • Current transformer for more accurate current measurement
  • higher accuracy classes 1; 0.5; 0.2 than with standard IE
  • Measurement in the frequency range 16 2/3 to 50kHz
  • Pulse measurement (e.g. 8/20μs)
  • low phase error for power measurement
  • very low remagnetization losses and
  • eddy current losses
  • Nanocrystalline toroidal cores with strip thickness of e.g. 20μm
  • electrically isolated primary and secondary circuits
  • Easy-to-install designs
  • versatile housing options with different through-holes

Advantages (Mechanical)

  • easy-to-install designs
  • versatile housing options with different through-holes

Typical Applications

Industry, Renewable Energies, Railway Technology, Measurement and Testing Technology, Energy, Automation and Building Technology

 

Type 1 3 5 10 25 50
Primary current [A] IPN 1 3 5 10 25 50
Max. primary current [A] ImaxPN 1,2 3,6 6 12 30 60
Secondary current [mA] IaN 20 20 20 20 25 50
Power [VA] Psek 0,05 0,05 0,05 0,05 0,063 0,25
Transformation ratio KN 50 150 250 500 1000 1000
Burden resistance [Ω] RB 125 125 125 125 100 100
Burden voltage [V] URB 2,5 2,5 2,5 2,5 2,5 5
Measurement accuracy 50 Hz [%] FU ≤1 ≤1 ≤1 ≤1 ≤1 ≤1
Ambient temperature [°C] TA -25 to +70 -25 to +70 -25 to +70 -25 to +70 -25 to +70 -25 to +70
Frequency range [Hz] f 0.05 to 50 0.05 to 50 0.05 to 50 0.05 to 50 0.05 to 50 0.05 to 50
Insulation test voltage
Primary/Secondary / 2 sec [kVac]
VP 3 3 3 3 3 3
PIN connection 3-4 / 2-1 3-4 / 2-1 3-4 / 2-1 3-4 / 2-1 NC / 2-1 NC / 2-1
Weight [kg] 0,05 0,05 0,05 0,05 0,05 0,07

Standards EN/IEC 61869-1/2

Type Connection
[mm²]
h
[mm]
b
[mm]
t
[mm]
DL
[mm]
s
[mm]
l
[mm]
a
[mm]
c
[mm]
IN/1 3-4 / 2-1 34 33 18 9 1,0 3,5 27,5 10
IN/3 3-4 / 2-1 34 33 18 9 1,0 3,5 27,5 10
IN/5 3-4 / 2-1 34 33 18 9 1,0 3,5 27,5 10
IN/10 3-4 / 2-1 34 33 18 9 1,0 3,5 27,5 10
IN/25 NC / 2-1 34 33 18 9 1,0 3,5 27,5 10
IN/50 NC / 2-1 38 38 20 13 1,0 6,5 30 10

All data and configurations can be found in our product datasheet.

Download Datasheet

Suitable for this product

Resistors

Current Transformer