Filter combinations, single-stage
Description
By using a mains choke, harmonics are reduced and the inrush current is limited. This improves efficiency and reduces the load on the line.
Benefits
- faster and more convenient installation
- small footprint
- Reduction of cable strands in the control cabinet
- Damping of current harmonics
- Choke with low noise due to vacuum impregnation
- Inrush current limitation
- Mains choke standard for short-circuit voltage of 4% at rated current
Typical applications
Suppression of frequency converters with IGBTs with simultaneous reduction of harmonics (according to VDE 0160/EN 61800-3 Class B)
- According to: IEC/EN 60939 / IEC 950 / UL 1283
- Test voltage: L-L 2100 V, DC 1s, L-PE 2700 V, DC 1s
- Overload: 1.5 x I 1 min/h
- Climate category: DIN IEC 68 Part 1 25/085/21
Type | Nominal voltage [V] |
Nominal current [A] |
Leakage current [mA] |
L [mH] | Cx [µF] | Cy [nF] | Rx [k] | Ry [k] |
CNW 304/80 | 3×400 | 80 | >35 | 1,2 | 1,5 | 600 | 560 | 560 |
CNW 304/120 | 3×400 | 120 | >35 | 0,5 | 3,5 | 870 | 560 | 560 |
CNW 304/150 | 3×400 | 150 | >35 | 0,6 | 3,5 | 870 | 560 | 560 |
Type | Connections | Dimensions [mm] | ||||||
Terminal | Ground | L 1 | L 2 | L 3 | B 1 | B 2 | H 1 | |
CNW 304/80 | 50 mm² | M10 | 330 | 315 | 290 | 190 | 120 | 216 |
CNW 304/120 | 50 mm² | M10 | 440 | 420 | 400 | 280 | 200 | 248 |
CNW 304/150 | 50 mm² | M10 | 440 | 420 | 400 | 280 | 200 | 248 |